START

Using This Quick Start Manual
Use this Quick Start Manual to set up your Strain Gage Meter and begin operation. Information is provided on how to:
ò Connect AC power
ò Connect the sensor
ò Set basic options for operation
ò Scale the meter.

For complete information on all setup options, please refer to the Strain Gage Meter Operator's Guide.

NOTE: This Quick Start Manual includes specific configuration parameters for bridge sensors with an output range of 0û100 mV and 10 V excitation. Other sensor types may require different parameters or additional ones. When this is the case, we refer you

Before You Begin
In addition to the meter and the related parts, you will need the following items to set up your unit:
ò 110 Vac power
ò Sensor
ò 1/8-inch flat-blade screwdriver.

Mount the Unit
1. Cut a panel opening using the dimensions shown below.
2.
Position the unit in the opening, making sure the front bezel is flush with the panel.
3. Install retaining clips on both sides of the meter and tighten against the panel.
Dimensions

Connect AC Power
1. Remove the panel at the back of the unit.
2. Locate the TB1 connector.


3. Insert the correct wire in each terminal as shown in the figure above and tighten the lockdown screws.

4. Tug gently on the wires to verify the connections.
Main AC Power Connections
Main AC Power Connections

Connect the Sensor
1. Locate the TB2 connector on the rear of the unit.

2. Attach the sensor wires and tighten the lockdown screws. The diagram below shows the wiring for bridge sensors with internal excitation. Refer to the Operator's Manual for setup requirements for other sensor types.

3. Tug gently on the wires to verify the connections.

4. Replace the panel at the back of the unit.
Bridge Sensor with Internal Excitation
Bridge Sensor with Internal Excitation

Turn On the Unit
1. Apply ac power.
As the unit initializes, RST flashes on the front panel, and then a numeric reading is displayed.

2. Verify that a numeric reading is displayed. If not:
ò Remove ac power
ò Verify the TB1 power connections
ò Check your power source
ò Apply ac power again.

Using the Configuration Menu
To configure the meter, you use the buttons on the front panel.
To:
Take This Action:
Display the Press the MENU button. The first function Configuration Menu on the menu, INPT, displays.
Select a submenu function 1. Press MENU until the function you function want is shown.
2. Press /TARE.
The information you can change flashes.
Select a value for that that submenu function 1. Press /NT/GRS to display the option you want.
2. Press MENU to store it.
"STRD" quickly flashes, indicating that the selection has been stored in memory. Then the next menu function displays.
Go back to the previous menu function Press RESET once.
Exit the Configuration Menu ò Press RESET twice. The unit displays "RST" as it reinitializes. When a numeric value displays, the unit is in the run mode.

ò Optionally, you can press MENU to move through all the menu functions until the unit reinitializes.

To Set the Input Type
1. Press MENU until the unit displays:
2. Press /TARE. The unit displays:
3. For this application you want 100M.

If 100M.is not displayed, press /NT/GRS until it appears. Other choices are 50 m, 10 V, 5 V, 0û20. Refer to the Operator's Manual for more information on changing ranges.

4.
Press MENU to select the sensor shown. The meter displays the next menu item. If you changed input type, the meter displays:

To Set the Decimal Point
1. If it's not already shown, press MENU until the unit displays:
2. Press /TARE.The unit displays:

3.
Press /NT/GRS to move the decimal point to the desired location. The factory setting is FFFF. The other choices are FFF.F, FF.FF, and F.FFF.


4.
Press MENU to select the decimal point position shown. The unit displays:

To Scale the Meter
You can scale the meter in one of two ways:
1. With a known load ù This method uses input (load) information sent from another device such as a scale or a simulator for voltage or current.
2. Without a known load ù This involves calculating the load based on transducer specifications and manually entering it to the meter.
For both methods, you must first identify the minimum input load (IN1) and the corresponding display reading you want (RD1). Then you identify the maximum input load (IN2) and its corresponding display reading (RD2).

NOTE: The decimal point is for display purposes only ù you set it where you want it to display for your application. When entering IN1 and IN2 values, ignore any decimal point on the display. However, you must enter RD1 and RD2 vaules with the decimal point in the desired position.

Scaling With Known Loads

To identify the minimum known load (IN1 and RD1):
1. If it's not already shown, press MENU until the unit displays:
2. Apply the minimum known load (0%).
3. Press /TARE The unit displays:
4. Press /TARE again. The unit displays the last setting for IN1.
5. Press /TARE again. The unit displays the actual reading being received from the sending device.
6. Press MENU to store IN1. The unit displays:

7.
Press /TARE The unit displays the last setting for RD1.
8. Change RD1 as necessary:
ò Press /TARE to scroll to the digit(s) you want to change (it flashes on the display).
ò Press /NT/GRS to change the value of the flashing digit. Values can range from 0 to 9. For the first digit, you can also enter a minus sign (û) or û1.

To identify the maximum known load (IN2 and RD2):

1. Apply the maximum known load (100%).
2. Repeat steps 4û9 for IN2 and RD2. Once you've completed all steps, the unit displays:
To begin operation:

Reinitialize the unit (press RESET twice or press MENU until RST flashes on the display). When a numeric reading appears, the unit is operational.
Scaling Without Known Loads
For 0û100 mV sensors, the values for the minimum and maximum input loads are always as follows:
    ò Minimum load (IN1) ù 0
    ò Maximum load (IN2) ù 9999.
If your installation uses a different sensor type, you must calculate the values for IN1 and IN2 before proceeding with the steps below. Use the formula provided in the Operator's Manual.

To define the minimum load (IN1 and RD1):
1. If it's not already shown, press MENU until the unit displays:(example on left)
2. Press /TARE. The unit displays:

3.
Press /TARE. again. The unit displays the last setting for IN1. (The first digit flashes.)

4. Change IN1 as necessary:
ò Press /NT/GRS to set or change the digit's current value. Continue to press /NT/GRS until the meter displays the desired value for the flashing digit. Values can range from 0 to 9. For the first digit, you can also enter a minus sign (û) or û1.
ò Press /TARE. to scroll to the remaining digit(s) you want to change.




5.
Press MENU to store IN1. The unit displays: (example on left)
6. Press /TARE.
The unit displays the last setting for RD1. (The first digit flashes.)

7. Change RD1 as necessary:


ò Press /NT/GRS until the meter displays the desired value for he flashing digit. Values can range from 0 to 9. For the first digit, you can also enter a minus sign (û) or û1.
ò Press /TARE. to scroll to the digit(s) you want to change.
8. Press MENU to store the value shown for RD1. The unit displays: (example on right)





To define the maximum load (IN2 and RD2):

1. Repeat steps 3û9 above, entering the values for IN2 and RD2.
2. Once you've com- pleted all steps, the unit displays: (example on right)
To begin operation: Reinitialize the unit (press RESET twice or press MENU until RST flashes on the display). When a numeric reading appears, the unit is operational.
Determining Reading Offsets
Meters scaled without known loads may reflect an offset in run mode. For example, say you set RD1 to 0 and RD2 to 100, but when the minimum load is applied, a value of û1.5 displays on the front panel.

To correct the reading offset:
1. With zero load applied, note the reading on the display.
2. Subtract that amount from the RD1 and RD2 values you originally entered.

In the example, the offset would be û1.5. If RD1 is to read 0 in run mode, it must be reentered as 1.5. RD2 must likewise be reentered as 101.5 if the meter is to read 100 when the maximum load is applied.

3. Repeat the steps for "Scaling Without Known Loads," but when the values for IN1 and IN2 display, do not change them. Instead, press MENU to move to the prompts for RD1 and RD2 and make the necessary changes.
4. Reinitialize the unit and resume operation.

 Home Home  Table of Contents TOC  Back Back